FOT Extinguishing Control Panel

FOT Extinguishing Control Panel

FOT-IVY is an extinguishing conventional fire control panel. The panel is designed for using together with systems for gas, powder, aerosol, water and other types of active extinguishing.

The panel is divided into two operation sections: extinguishing and fire. FOT-IVY has 3 wire zones – 2 for activation of automatic fire detectors and 1 conventional fire zone which supports up to 32 detectors. Automatic and manual operation modes (selectable via 3 positional key lock) and a special button for manual realize of the extinguishing process. The panel is designed for operation with solenoids, pressostats and other kind of actuators. Optional LOG module can be added to the FOT-IVY’s configuration for reviewing of recorded memory events.

FOT-IVY extinguishing control panel is designed according to EN12094-1 and EN54-2/4 standards.

Description:

  • 2 Conventional Zones for extinguishing
  • 1 Conventional Zone for Fire Alarm
  • Low Pressure input – supervised balanced input
  • Manual release input – supervised balanced input
  • Mode select input – supervised balanced input for switching between Manual and Automatic operation mode
  • Hold input – supervised balanced input
  • Enable/Disable – supervised balanced input

Flow Control – supervised balanced input